Mitsubishi Electronics FX3U User Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 284
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
A - 11 A - 11
Caution to conform with EC Directives
Installation in Enclosure
Programmable logic controllers are open-type devices that must be installed and
used within conductive control cabinets. Please use the programmable logic
controller while installed within a conductive shielded control cabinet. Please secure
the cabinet door to the control cabinet (for conduction).
Installation within a control cabinet greatly affects the safety of the system and aids
in shielding noise from the programmable logic controller.
Control cabinet
- The control cabinet must be conductive.
- Ground the control cabinet with the thickest possible grounding cable.
- To ensure that there is electric contact between the control cabinet and its door,
connect the cabinet and its doors with thick wires.
- In order to suppress the leakage of radio waves, the control cabinet structure must
have minimal openings. Also, wrap the cable holes with a shielding cover or other
shielding devices.
- The gap between the control cabinet and its door must be as small as possible by
attaching EMI gaskets between them.
*1. These wires are used to improve the conductivity between the door and control
cabinet.
Shielding cover
Shielded cable
Wires*1
EMI gasket