MELSEC-A
5 PROGRAMMING
(1) Program example for power-on
S
etting of
n
etwork
p
arameters
S
etting of
a
utomatic
r
efresh
p
arameters
Synchronization
mode invalid
Dedicated instruction
(RLPA)
Starting I/O number of
master module
Parameter storage
starting device
Device which turns on 1
scan at completion
Reads parameter status
at abnormal completion.
Sets RX starting number.
Sets "X".
Sets X100.
Sets RY starting number.
AJ65SBT-64AD station
information (remote
device station, 1 station
occupied, station No. 1)
Number of connected
modules:1
Sets 32 points.
Sets "Y".
Sets Y100.
Sets 32 points.
Sets RW starting number.
Sets "D".
Sets D200.
Sets 260 points.
Sets SB starting number.
Sets "B".
Sets B0.
Sets 512 points.
Sets SW starting number.
Sets W0.
Sets "W".