Mitsubishi Electric Air Conditioning Network System
BACnet
TM
Interface: PAC-YG31CDA (Ver. 1.30)
Operation Manual
Contents
1.Safety Precautions1
2.System Requirements ……2
3.System Configuration4
4.Functional specification 6
5.Installation 16
6.Part Name and Functions ………20
7.Initial Startup and Shutdown ………22
8.System Setting Procedure ………22
9.Site Adjustment ………33
Appendix1: Auto Log – In Confirmation Method
Appendix2: Initial Value
Appendix3: Correcting the system setting data when
PC fails or is replaced.
Please read this manual before using the unit.
Please keep this manual for future use. WT04221X03
2004-Mar. (Ver. 1.30)
Page view 0
1 2 3 4 5 6 ... 45 46

Summary of Contents

Page 1

Mitsubishi Electric Air Conditioning Network System BACnetTM Interface: PAC-YG31CDA (Ver. 1.30) Operation Manual

Page 2 - Appendix 2: Initial Value

4.Functional specification 4.1 Communication Protocol Specification 1) Protocol Outline BACnet/IP which applied to ANSI/ASHRAE 135-1995, 135a, 13

Page 3

4.2 Object List The list of the objects to be used is shown below. Object type Support ¡: Support ×: Un-supporting Note Analog Input 0 ¡ Analog Out

Page 4 - 1. Safety Precautions

4.3 Object and Management Item Object ID consists of object type + instance number. An instance number consists of G-50A number + air-conditioner equ

Page 5 - 3. Other Precautions

Object Object type Instance number Management item Note Prohibition of local operation (filter reset) Binary Value xxxx15 Inactive: Permit Active: Pro

Page 6

4.4 Service List Service Initiate Execute Note Acknowledge Alarm 0× × Confirmed COV Notification 1¡ × Confirmed Event Notification 2¡ × Get Alarm

Page 7 - 2.3 Restrictions

4.5 Service list for every object Service transceiver list for every object is shown below. INIT : BACnet IF transmits. EXEC : BACnet I

Page 8

4.6 Event Service specification It is shown whether Event Notification of each object is carried out or it does not carry out. Event is used for the

Page 9 - 3.3 Group Configuration

4.8 Setting functional list The list of the setting functions of BACnet IF is arranged below. Chapter 8 explains the usage of each

Page 10 - 4.Functional s

5.Installation 5.1 Pre-installation Steps Preparing for installation Before installing BACnet IF program, do the following checks and pr

Page 11 - 4.2 Object List

5.2 BACnet IF Setup This section describes how to set up BACnetIF and a setting tool (SetBACnet). (1)CD-ROM directory structure The fo

Page 12 - and 6 figures): X X XX XX

Contents 1.Safety Precautions ………1 2.System Requirements

Page 13

(5) Check the installation folder Check the location where the program is to be installed. If the location needs to be changed, set the n

Page 14 - 4.4 Service List

5.3 BACnet IF Uninstall This section describes how to uninstall “BACnet IF ” and “Setting Tool (SetBACnet) “ program. (1) Uninstall 1) Chec

Page 15

6.1 Window Elements The icon is displayed on the taskbar by the completion of starting of BACnet IF program. Click the BACnet IF icon on a taskbar

Page 16 - 4.7 Function

7. Initial Startup and Shutdown 7.1 Before Startup Before starting BACnet IF program, do the following checks. No. Item (1) A test run of the air

Page 17 - 4.8 Setting functional list

3) Push [Alt] and [F4] buttons. The confirmation screen will open. 4) Click the [Yes] button. The confirmation screen will open again. 5) Click

Page 18 - 5.Installation

8. System Setting Procedure Setting Tool [SetBACnet] is the program that sets up the function and system configuration of BACnet IF. Please restart

Page 19 - 5.2 BACnet IF Setup

8.3 Windows Elements The initial setup screen of SetBACnet is shown below. Title bar: Show the title of thewindow. Menu bar: Show a list of funct

Page 20

8.6 System Setting Procedure The following is an explanation of the System Settings performed at Setting Tool. Step1: G-50A connection set-up S

Page 21 - 5.3 BACnet IF Uninstall

8.7.2 G-50A NO. and IP-Address Set the number and IP-Address of G-50A connected to the system. Item Contents Set value No. (G-50A No.) *1 S

Page 22 - .Part Names and Functions

(4) from G-50A Click the [from G-50] button. The confirmation screen will open. Click the [YES] button acquires group information from G-50A. Note: Se

Page 23 - and Shutdown

In this manual, Microsoft® Windows® XP Professional is called Windows XP. Trademarks MS, Microsoft, Microsoft logo, and Windows are registered tra

Page 24

8.8 Setup for BACnet BACnet communication is set up. 8.8.1 Communication setup Item Contents Set value Broad Cast IP Address Input the IP addres

Page 25 - Procedure

8.8.2 Notification Setting BMS carries out the monitor of the state, in order to know the state of Object of BACnetIF. Notification is the functio

Page 26 - 8.5 Get/Put system settings

(2) Modify notification address Click the [Modify] button. The [Notification Address] screen will open. (3) Delete notification address Click

Page 27 - 8.7 Setup for G-50A

Notification Class Setting Notification Class is set up for every Notification Class. (1) Add notification class Click the [Add] button. The [No

Page 28

Item Contents Set value IP Address Input the IP address to notify, The devices, which communicate on BACnet makes a network address the sam

Page 29

8.9 System Setup The extended function of a system is set up. Parameter Contents Value Unit Of temperature It is on BACnet communication and is

Page 30 - 8.8 Setup for BACnet

9. Site Adjustment 9.1 Site Adjustment When the task of site adjustment is subdivided into smaller tasks as shown in the figure below, the tasks c

Page 31

9.2 Tools for Site Adjustment You will need the following equipment and reference material in order to easily carry out site adjustment. Item Cont

Page 32

9.4 Step 2: Initial setting of BACnet IF LANStep 2 HUB Power supply unitG-50A BACnet IF Ether BACnet Building Automation System

Page 33 - Notification Address Setting

9.5 Setting Check Follow a setting item checklist according to each function you want to use. Item Point Target G-50A setup IP Address Is it in ag

Page 34

1. Safety Precautions· Please read the Safety Precautions section very carefully before using the unit. · The safety cautions provided here are ve

Page 35 - 8.9 System Setup

9.6 Step 3: Test operation from BMS (Building Management System) LANEther BACnet Building Management System BACnet IF G-50A Power supply unitHUB St

Page 36 - 9. Site Ad

BACnet Interface PAC-YG31CDA Site Adjustment sheet G-50A Number [ ] IPaddress[ . . . ] Group N

Page 37

Object Object type Instance number *5) Management item Test procedure Result Prohibition of local operation (Mode) BV xxxx14 Inactive: Permit

Page 38

Appendix 1: Auto Log – In Confirmation Method This chapter describes the procedure for confirming that the Auto login setting is validated. 1)

Page 39 - 9.5 Setting Check

The initial value of the property of each object is shown. Object Object Type Instance Number Present Value Note On/Off (setup) BO xxxx01 OFF (0)

Page 40

Appendix 3: Correcting the system setting data when PC fails or is replaced. When PC, which set up BACnet, breaks down or it replaces, how to rest

Page 41 - Adjustment sheet

HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN W

Page 42

Safety Guidelines for the Computer Running the Integrated PAC-YG31CDA Software (Summary) 1. Selecting a Computer Selecting a desktop · Depending

Page 43

2.System Requirements 2.1 Requirements (system recommendations) We recommend the following software and hardware when using this application (PAC

Page 44

2.3 Restrictions The following restrictions apply to the BACnet IF program. (1) System configuration limits Number of units Note G-50A Max. 10

Page 45

3.System Configuration 3.1 System Configuration Example Power supply unitG-50AG-50A[Image drawing] Indoor unit Outdoor unitLANHUB BACnet IF Soft

Page 46

3.3 Group Configuration In BACnet IF, a G-50A number + group number is a unit for management. The instance number of BACnet consists of G-50A numbe