Mitsubishi Electronics PAC-YG31CDA User Manual Page 29

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 28
(4) from G-50A
Click the [from G-50] button. The confirmation screen will open.
Click the [YES] button acquires group information from G-50A.
Note:
Separately, it is necessary to register groups into G-50A.
8.7.4 Group setup
8.7.4.1 Group Setup
Item Contents Set value
Group No Input the number of a group. Default: Null
Range: 1 to 50
Model Select the model of a group.
IC:Indoor unit
LC: LOSSNAY unit
OA processing unit: select IC
Out Of Service *1 If the service mode of the group is changed
into OutOfService, the communication
message about the group will be
transmitted to neither G-50A nor a BMS.
Default: Off
Check mark is Off: Service mode
Check mark is On: OutOfService
mode
*1:Out Of Service in the case of maintenance or a test run.
Communication Message
From BMS : The instruction (System Forced OFF is excluded) from BMS is not transmitted to G-50A.
Monitoring for G-50A : Neither state change nor abnormality of the air-conditioning unit is notify.
Change Timing
After ending BACnetIF, with [OutOfService] checked, a setup is reflected at the time of next BACnetIF starting.
If [OutOfServie] is checked and the [Online Operation] button is clicked, it will be immediately reflected in BACnetIF. Refer to 8.7.4.2
Note:
Be sure to release OutOfService mode after maintenance or a test run.
8.7.4.2 Online Operation
Click the [Online Operation] button. The confirmation screen will open.
If it will be immediately reflected in BACnet IF, click the [True] button.
Click the [False] button, when that is not right.
26
Page view 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 45 46

Comments to this Manuals

No comments